0: H = turns on/off a heater; C = turns on/off a fan
1: temperature difference from set temperature target to initiate on/off pending P0- usually set this to at least 1degC to minimise excessive cycling
eg. for P0=C, and target set to 32deg and P1 set to 2deg, the fan will turn on when temperature hits 34deg and turn off when it falls to the target of 32deg
eg. for P0=H, and target set to 20deg and P1 set to 2deg, the heater will turn on when temperature falls below 18deg and turn off when it rises to the target of 20deg
2: maximum temperature - if goes above this it will turn off
3: minimum temperature - if goes below this it will turn off
4: thermometer correction value - allows you to correct the thermometer reading Default = 0degC
5: the all important delay start in minutes - set this to a reasonable delay to avoid excessive cycling and adds to the P1 behaviour
6: is the alarm temperature which will turn off the device if temp is reached (this can be disabled by setting it to OFF by going above 120deg when setting the value)
7: allows locking the temperature/value change buttons
8: factory reset (this can also be down by holding both up and down arrows for a few seconds)